AC Load Monitor Los Angeles CA

A simple circuit monitors the elapsed time over which a line-connected ac load energizes. You can then access the elapsed-time count over a standard one-wire protocol.

Local Companies

Computer Works
(323) 525-0056
7825 Beverly Blvd
West Hollywood, CA
Softlink America Inc
(323) 525-1931
327 N Gardner St
West Hollywood, CA
Torah On The Line
(323) 939-8672
332 N Detroit St
West Hollywood, CA
R Lw. Concepts
(323) 938-6287
403 S Curson Ave
West Hollywood, CA
E C Computer Systems
(323) 464-2533
1540 N Highland Ave
West Hollywood, CA
We Rent Computers
(310) 289-7979
8504 W 3rd St
West Hollywood, CA
Alpha Base Systems Inc.
(323) 850-6575
7551 W Sunset Blvd
West Hollywood, CA
Computer Wiz
(323) 851-4000
1452 N Martel Ave
West Hollywood, CA
Electronics Boutique
(323) 845-9685
7100 Santa Monica Blvd
West Hollywood, CA
Enhancement Software
(323) 850-1362
2129 Mount Olympus Dr
West Hollywood, CA

provided by: EDN

A simple circuit monitors the elapsed time over which a line-connected ac load energizes (). You can then access the elapsed-time count over a standard one-wire protocol. When you energize the ac load, the optoisolator provides pulses at the ac-line frequency to the input of the one-wire counter, a DS2423 IC. Thus, the counter continuously increments whenever you energize the load. Resistors R1 and R2 limit the current, and diode D1 protects the optoisolator from reverse-polarity voltages during the negative half of the line cycle.

As an example, the circuit can monitor the duration of operating intervals for a 240V-ac well pump, thereby giving an indirect measure of the amount of water the well pumps and the approximate amount of power it consumes. The one-wire master counter-a Linux-based PC, for example-reads the elapsed count once per minute. Any change in the count from one reading to the next indicates that the pump is energized and running, and you calculate the length of time in seconds by simply taking the difference in counter values divided by the line frequency-60 Hz, in this case. The time in seconds equals the new count minus the old count divided by 60 Hz.

The circuit can monitor a water heater, a furnace, an air-conditioning unit, or any other ac-connected load. You may need to adjust the R1 and R2 values to accommodate line voltages other than 240V ac or the characteristics of other optoisolators. You can also monitor two independent loads by attaching a second optoisolator circuit to the Counter B input of a single DS2423.



author: Michael Petersen, Maxim Integrated Products, Sunnyvale, CA

EDN. Copyright © 2007 Reed Business Information, a division of Reed Elsevier Inc. All rights reserved.