POWER-LIMITED FIRE ALARM CABLES CONTINUED Saint Louis MO

The following contains home security information you should know about power-limited fire alarm cables. Read on if you or a loved one is interested in home improvement and security in Saint Louis.

Local Companies

Burnes Citadel Security Co
314-771-7275
5027 Columbia Ave
St. Louis, MO
All Auto Alarm Center
314-351-3131
4611 S Kingshighway Blvd
St. Louis, MO
Alarm Monitoring Company
314-644-5255
2001 S Hanley RD
St. Louis, MO
Adt Security Services Incorporated
314-436-2168
926 Lasalle Park Ct
St. Louis, MO
Hackett Security
314-432-4200
9811 S Forty Dr
St. Louis, MO
Gateway Alarm Inc
314-487-2224
5923 Weber Rd
St. Louis, MO
Senna Systems Inc
314-785-1201
9291 Watson Ind Park
St. Louis, MO
Acf Alarm Co
314-869-8500
9021 Riverview DR
St. Louis, MO
ADI Distributors
314-993-4010
2238 Ball DR
St. Louis, MO
Pass Security
(314) 241-0422
Saint Louis, MO

provided by: 

DIGGING FOR AN ANSWER TO UNDERGROUND CABLE

Q As a follow up to last month's questions on Power-Limited Fire Alarm Cables (FPL), is there a requirement to use FPL in conduit that is installed underground from one building to another building? The Authority Having Jurisdiction (AHJ) says I always have to use "fire alarm cable."

A No. Type FPL is meant to be installed exposed in a building, and when following the rules from Article 760.15, Part B, conduit isn't necessary. To be given the FPL designation is to indicate that the conductor's insulation/jacket will be "resistant to the spread of fire," which is not a factor with buried cable.

Therefore, since FPL is not approved for "wet locations" and there is no such thing as "direct burial FPL cable," you are left with choosing one of three methods. Which method you choose will probably depend on how much you like to dig:

METHOD #1.METHOD #2.METHOD #3.
Use Direct Burial Cables or Conductors.Use Nonmetallic Raceways Listed for Direct Burial Without Concrete Encasement or Other Approved Raceways.Use Rigid Metal Conduit or Intermediate Metal Conduit.
Only copper conductors are permitted for fire alarm use (stranded or solid).Cables and insulated conductors installed in enclosures or raceways in underground installations shall be listed for use in wet locations.Cables and insulated conductors installed in enclosures or raceways in underground installations shall be listed for use in wet locations.
310.7 Direct burial cables or conductors. Conductors used for direct burial applications shall be of a type identified for such use.i.e. MTW, RHW, RHW-2, TW, THW, THW-2, THHW, THHW-2, THWN, THWN-2, XHHW, XHHW-2, ZW (or Direct Burial cables).i.e. MTW, RHW, RHW-2, TW, THW, THW-2, THHW, THHW-2, THWN, THWN-2, XHHW, XHHW-2, ZW (or Direct Burial cables).
Bury it at least 24 inches deep.Bury it at least 18 inches deep.Bury it at least 6 inches deep.

GREG KESSINGER, SET, CFPS, president of an alarm installing company since 1981, teaches NICET training classes to fire alarm system designers and installers and continuing education seminars for Ohio's fire alarm inspectors. You can reach him at 888-910-2272; e-mail: Greg@firealarm.org; or visit his website at www.FireAlarm.org.

author: By Greg Kessinger