POWER-LIMITED FIRE ALARM CABLES CONTINUED Wichita KS

The following contains home security information you should know about power-limited fire alarm cables. Read on if you or a loved one is interested in home improvement and security in Wichita.

Local Companies

Westar Security
(785) 232-6396
800 E Waterman St
Wichita, KS
Central Key & Safe
(316) 262-6144
305 N Market St
Wichita, KS
Audio Visual Architects
(316) 941-4484
PO Box 332
Wichita, KS
Securitynow
(316) 361-0654
915 W Douglas Ave
Wichita, KS
Great Plains Communications
(316) 942-7272
1809 S West St
Wichita, KS
GreenBuilt Company Security Division
(316) 265-5492
1556 Palisade St
Wichita, KS
ProTec Security Services Inc
(316) 796-0096
1999 Amidon St
Wichita, KS
Secure Net Alarm Systems
(316) 942-4474
1809 S Hoover
Wichita, KS
Automatic Music & Vending
(316) 522-2200
1813 S Florence St
Wichita, KS
Digital Age Security & Surveillance
(316) 944-5666
4233 W Central
Wichita, KS

provided by: 

DIGGING FOR AN ANSWER TO UNDERGROUND CABLE

Q As a follow up to last month's questions on Power-Limited Fire Alarm Cables (FPL), is there a requirement to use FPL in conduit that is installed underground from one building to another building? The Authority Having Jurisdiction (AHJ) says I always have to use "fire alarm cable."

A No. Type FPL is meant to be installed exposed in a building, and when following the rules from Article 760.15, Part B, conduit isn't necessary. To be given the FPL designation is to indicate that the conductor's insulation/jacket will be "resistant to the spread of fire," which is not a factor with buried cable.

Therefore, since FPL is not approved for "wet locations" and there is no such thing as "direct burial FPL cable," you are left with choosing one of three methods. Which method you choose will probably depend on how much you like to dig:

METHOD #1.METHOD #2.METHOD #3.
Use Direct Burial Cables or Conductors.Use Nonmetallic Raceways Listed for Direct Burial Without Concrete Encasement or Other Approved Raceways.Use Rigid Metal Conduit or Intermediate Metal Conduit.
Only copper conductors are permitted for fire alarm use (stranded or solid).Cables and insulated conductors installed in enclosures or raceways in underground installations shall be listed for use in wet locations.Cables and insulated conductors installed in enclosures or raceways in underground installations shall be listed for use in wet locations.
310.7 Direct burial cables or conductors. Conductors used for direct burial applications shall be of a type identified for such use.i.e. MTW, RHW, RHW-2, TW, THW, THW-2, THHW, THHW-2, THWN, THWN-2, XHHW, XHHW-2, ZW (or Direct Burial cables).i.e. MTW, RHW, RHW-2, TW, THW, THW-2, THHW, THHW-2, THWN, THWN-2, XHHW, XHHW-2, ZW (or Direct Burial cables).
Bury it at least 24 inches deep.Bury it at least 18 inches deep.Bury it at least 6 inches deep.

GREG KESSINGER, SET, CFPS, president of an alarm installing company since 1981, teaches NICET training classes to fire alarm system designers and installers and continuing education seminars for Ohio's fire alarm inspectors. You can reach him at 888-910-2272; e-mail: Greg@firealarm.org; or visit his website at www.FireAlarm.org.

author: By Greg Kessinger


Featured Local Company

Westar Security

(785) 232-6396
800 E Waterman St
Wichita, KS

Related Local Events
Chamber Meetings
Dates: 7/2/2009 - 7/2/2009
Location: Kingman City Hall
Kingman, KS
View Details

Retail Committee
Dates: 6/22/2009 - 6/22/2009
Location: Mollie's Attic
Kingman, KS
View Details